Title: Energy Performance of Eco-friendly R152a and R600a Refrigerants as Alternative to R134a in Vapour Compression Refrigeration System
Authors: Bolaji, Bukola Olalekan
Huan, Zhongjie
Borokinni, Francis Olusesi
Keywords: alternative refrigerants
eco-friendly
energy
performance
Issue Date: 2014
Publisher: Analele Universitatii Eftimie Murgu, Eftimie Murgu University of Resita, Romania.
Series/Report no.: Volume 21;No. 3, pp. 354-367
Abstract: In this study, the energy performance of eco-friendly refrigerants (R152a and R600a) was investigated theoretically as alternative to R134a in refrigeration system. The results showed that the vapour pressure and specific volume of R152a are very close to those of R134a. R152a emerged as the most energy efficient with average Power Per Ton of Refrigeration (PPTR) of 10.6% less than that of R134a. R152a also exhibited higher Volumetric Refrigerating Capacity (VRC) and Coefficient of Performance (COP) than both R600a and R134a. The average COPs obtained for R152a and R600a were 13.4% higher and 5.4% lower than that of R134a, respectively. Generally, R152a performed better as R134a substitute in that it has the lowest PPTR, highest thermal conductivity, refrigerating effect, VRC and COP.
URI: http://repository.fuoye.edu.ng/handle/123456789/1271
Appears in Collections:Mechanical Journal Publications

Files in This Item:

File Description SizeFormat
74-2014 Bolaji-Huan-Borokinni UEM21(1)354-367 Ecofriendly R152a&R600a ‎.pdf368.88 kBAdobe PDFView/Open
View Statistics

Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.

 

Valid XHTML 1.0! DSpace Software Copyright © 2002-2010  Duraspace - Feedback